Ignition voltage setting

Last modified by Андрей Калиновский on 2023/04/26 11:14

1) Analyzing the navigation report, we determine the change in voltage in motion. The figure shows that in motion it becomes more than 13V, and during parking - less than 13V.

image-20230425141606-1.png

2) We start the “Onboard voltage” sensor in the object card with the upit alias and the calibration table. Input type 0 - diagnostic, input number - 0.

image-20230425141618-2.png

3) We start a virtual sensor "Ignition" in the object card with an aggregating function "expression" and an indication of the formula if(upit>13,true,false) where upit is a link to the "Onboard voltage" sensor, and 13 is the voltage limit, after which the sensor should turn on. Do not enter anything in the Alias ​​field.

image-20230425141622-3.png

4) Check the operation of the sensor:

image-20230425141627-4.png

Addition 1. 

If the object was set to ignition by voltage, and after some time there are voltage drops or loss (malfunction of the battery / generator / wiring or other), as a result of which the ignition operation has ceased to be detected partially or completely, then the runs and tracks can be restored as follows :

Step 1) On the Monitoring tab , select the desired object and click on the edit button, then in the Object editor window , select the templates tab;

image-20230425141632-5.png

Step 2) From the list of templates, we need a Stop template , select it and press the edit button ;

image-20230426111413-1.png

Step 3) In the template editor window Stop , in the Basic conditions for defining an event , delete the event - Ignition off ;

image-20230425141814-12.png

Step 4) Press the save button in the template editor window Stop ;

image-20230425141819-13.png

Step 5) We also press the save button in the Object editor window .

image-20230425141823-14.png

After these steps, the object will have a track and mileage, both on the map and in reports, regardless of the faulty ignition.

Examples:

Correct ignition

image-20220915144625-7.jpeg

Faulty ignition

image-20220915144651-8.jpeg

After editing the template

image-20221007171745-3.jpeg

Addendum 2.

After the fault with the voltage on the object is eliminated, we can return the template to the default settings, for this:
Step 1) Go to the Object editing   and click on the Templates tab ;
Step 2) From the list of templates, we need a Stop template , select it and click the edit button;
Step 3) In the template editor Stop , press the button Default , a window will appear on the successful reset of user settings to the basic ones, press OK;

image-20220915153525-6.jpeg

image-20220915145718-11.jpeg
Step 4) In the Stop template editor , click save;
Step 5) In the Object editor , click save.
After these steps, the basic settings of the Stop template for the ignition sensor are restored.

   

Menu

GLONASSSoft wiki - 2023 г